NEC 310.16 · 2023

Wire Size Calculator

Size a branch circuit or feeder in one pass: ampacity with derating, terminal ratings, continuous loads and voltage drop — the larger answer wins.

Result

Recommended wire size
8 AWG
Usable ampacity
50 A (needs 40.0 A)
By ampacity alone
8 AWG
By voltage drop alone
8 AWG
Voltage drop at this size
4.69 V · 1.95%

Correction ×1.00 (ambient) · adjustment ×1.00 (conductors), from the 90 °C column, capped at the 75 °C terminal rating.

Based on NFPA 70 (NEC) 2023 tables. An estimating aid, not an engineering design: confirm sizes against the code edition your authority having jurisdiction enforces, local amendments and manufacturer data.

How the wire size is chosen

  1. Required current = load × 1.25 if continuous.
  2. For each size, take the Table 310.16 ampacity for the insulation rating, apply the ambient and conductor-count factors, then cap it at the terminal column. The first size that carries the required current — and that 240.4(D) lets you protect at that current — is the ampacity answer.
  3. Separately, find the smallest size whose voltage drop over the run stays under your limit.
  4. Use the larger of the two.

Frequently asked questions

What size wire do I need for 40 amps?

8 AWG copper at 75 °C terminals (50 A) for a 40 A non-continuous load on a short run — 10 AWG copper is only 35 A at 75 °C, and NEC 240.4(D) limits its breaker to 30 A. If the 40 A is continuous it must be sized for 50 A, which 8 AWG copper still meets. Long runs may need a bigger wire for voltage drop; enter the length to check.

Why can’t I use the 90 °C column?

You start derating from the 90 °C column when the insulation is rated 90 °C (THHN, XHHW-2), but the final ampacity can’t exceed the rating of the terminals it lands on — usually 75 °C, and 60 °C for many devices rated 100 A or less (NEC 110.14(C)). The calculator applies both.

What is the 125 % rule?

A continuous load — maximum current expected for three hours or more — must be served by conductors rated at least 125 % of that load (NEC 210.19(A)(1) and 215.2(A)(1)). A 32 A EV charger therefore needs a conductor good for 40 A.

How do more wires in a conduit change the size?

With more than three current-carrying conductors in a raceway, NEC Table 310.15(C)(1) reduces each conductor’s ampacity: 80 % for 4–6, 70 % for 7–9, 50 % for 10–20 and so on. Equipment grounds don’t count; a neutral counts only when it carries unbalanced or harmonic current.

Copper or aluminum?

Aluminum carries less current per size — roughly two AWG sizes larger than copper for the same ampacity — and has higher voltage drop, but it is lighter and much cheaper for feeders. It is common from about 1 AWG up; terminals must be rated AL/CU.

Sizing one run is easy. Counting a whole job isn't.

Aginera reads your electrical drawings and counts devices, fixtures and panels, measures conduit and feeder runs, and builds the takeoff with a sheet reference for every number.

More calculators: Conduit Fill Calculator · Voltage Drop Calculator